What is an IPS?

An IPS (Instant Power Supply) is a home backup system — an inverter, a battery bank and a charger in one unit — that switches to battery power automatically when the mains fails. The term IPS is used across Bangladesh for what other markets call an inverter battery system or home UPS. While mains power is present, the IPS passes it through to your fans, lights and sockets and quietly charges its batteries. The moment power cuts, the inverter converts the batteries' DC into AC and your loads keep running, usually with a blink so short most appliances never notice. When mains returns, the IPS switches back and recharges the bank for the next outage.

Every IPS buying decision is really two decisions: how big the inverter must be, measured in VA, to run your load at all, and how big the battery bank must be, measured in amp-hours (Ah), to run it for as long as you want. Buyers routinely get one of the two wrong — an inverter too small for the load, or a battery that promises a night of backup and delivers an hour. This ips calculator exists to size both halves openly, from your actual appliance list, using the same formula sellers and engineers use, so you can check any quote against your own arithmetic before you pay.

The IPS sizing formula

IPS battery formula: Required Ah = (Load W × Backup hours) ÷ (Battery V × Inverter efficiency × Depth of discharge). Inverter size: VA = Load W ÷ 0.8 power factor, plus 20% headroom, rounded up to a standard rating. This page implements exactly these two formulas.

Read the battery formula from left to right and each term earns its place. Load times hours is the energy you want delivered, in watt-hours. Dividing by battery voltage converts that energy into amp-hours at your system voltage. Efficiency then takes its cut: an inverter that is 80% efficient wastes a fifth of the battery's energy as heat, so the bank must be bigger by that factor. Depth of discharge takes the second cut: a lead-acid battery that you only dare use halfway must be twice the nameplate size of the energy you plan to draw. Ignore either factor — as many rule-of-thumb charts do — and the system you buy delivers roughly half to two-thirds of the backup you expected.

The VA formula is simpler but just as often skipped. Inverters are rated in volt-amps, loads are labelled in watts, and the two differ by the power factor: watts = VA × power factor. With the typical 0.8 power factor of home IPS units, a 500 W load already needs 625 VA before any margin. This calculator then applies 20% headroom and rounds up to a standard rating — 400, 600, 800, 1,000 VA and upward — because motors and fridges draw starting surges well above their running watts, and an inverter run flat-out at its limit runs hot and ages fast.

Worked example: 500 W for 4 hours

Take a home that wants to run 500 watts of fans, lights and a TV for 4 hours, on a 12 volt lead-acid system with 80% inverter efficiency and 50% depth of discharge. The formula gives Required Ah = (500 × 4) ÷ (12 × 0.80 × 0.50) = 2,000 ÷ 4.8 = 416.7 Ah, stated as 417 Ah required. In standard 200 Ah batteries that is 417 ÷ 200, rounded up — three 200 Ah batteries' worth of capacity (two batteries give only 400 Ah, just short of the requirement). The inverter size is 500 ÷ 0.8 = 625 VA, and with headroom the recommendation is an 800 VA class IPS. Every figure here is reproduced by the calculator above — set a single 500 W custom load with the same settings and check it yourself.

The same 500 W, 4-hour job at higher system voltages shows why voltage choice matters. At 24 V the requirement is (500 × 4) ÷ (24 × 0.80 × 0.50) = 208 Ah, met by 2 parallel strings of 2 batteries in series — 4 batteries total. At 48 V it is 104 Ah, met by a single string of 4 in series. The stored energy is nearly identical in all three systems; what changes is the current, the cable thickness and the battery arrangement, which the next sections cover.

System voltageRequired Ah200 Ah batteries (series × parallel)Total batteries
12 V417 Ah1 × 33
24 V208 Ah2 × 24
48 V104 Ah4 × 14

Building your load: typical appliance watts

Sizing starts with an honest load list. The wattages in the load builder are typical running figures for common Bangladeshi home appliances, and the table below is the exact dataset the calculator uses. A ceiling fan at about 75 W and an LED light at about 12 W are the backbone of most IPS loads, which is why a modest IPS can keep a home comfortable through an outage: five fans and six lights together draw under 450 W. The heavy items are the fridge, at about 150 W running, and a desktop computer at about 200 W — and anything with a heating element, such as a kettle, iron or rice cooker, usually exceeds a home IPS entirely and should stay off the backup circuit.

ApplianceTypical watts used hereNote
Ceiling fan75 WOlder fans can draw 90–100 W; BLDC fans far less
LED light12 WPer bulb or tube light
TV100 WLED TV, mid-size; larger sets draw more
Fridge150 WRunning watts; compressor cycles and surges on start
Computer200 WDesktop with monitor; laptops draw 45–65 W
Wi-Fi router10 WRouter plus ONU/ONT is usually 10–15 W
CustomYour figureRead the rating plate: watts, or volts × amps

Two habits make the load list trustworthy. First, size for the load that will actually run together at the worst moment — a hot evening outage with every fan on — not the average. Second, check rating plates where you can: appliance watts vary by model and age, and a 20% error in load flows straight through the formula into a 20% error in battery size. The custom row exists for exactly this: enter the plate watts of anything unusual and the builder treats it like any preset appliance.

Series, parallel and how many batteries

Home IPS batteries are almost always 12 V units, whatever the system voltage. To build a 24 V bank you wire two in series — voltages add, amp-hours stay the same. To add capacity you wire strings in parallel — amp-hours add, voltage stays the same. So the battery count has two steps: series count is system voltage ÷ 12 (1, 2 or 4 for 12, 24 or 48 V), and parallel strings are the required Ah ÷ chosen battery size, rounded up. Total batteries = series × parallel. That is why the 24 V worked example needs 4 batteries even though its 208 Ah sounds smaller than the 12 V system's 417 Ah: each string carries two batteries, and two strings are needed to pass 200 Ah.

Keep parallel strings few and equal. Batteries in a bank should be the same model, age and capacity, wired with equal-length cables, or the weakest and worst-connected battery drags the rest down — Victron's Wiring Unlimited guide, listed in the sources, covers bank wiring in depth. In practice, if a 12 V design needs more than three or four parallel strings, that is the signal to move up to 24 V or 48 V instead, where the same energy needs fewer parallel strings and thinner cables for the lower current.

Choosing the inverter (VA) size

The inverter must do two jobs: carry the running load continuously, and survive the starting surge of anything with a motor. Fans, fridges and pumps can draw three to seven times their running watts for the first fraction of a second. A unit sized exactly at the running VA may trip or refuse to start a fridge even though the steady maths fits. That is why this calculator divides watts by the 0.8 power factor and then adds 20% headroom before rounding up to a standard rating — 500 W becomes 625 VA on paper and an 800 VA class recommendation in the shop.

Also check what the VA rating does not tell you: whether the output is pure sine wave or modified sine wave (fans and motors run quieter and cooler on pure sine), the surge rating in VA and how long it can be sustained, and the charger size in amps, which decides how fast a drained bank refills before the next outage. A big battery behind a small charger is a common hidden mismatch in packaged deals, and no sizing formula can fix it after purchase.

Depth of discharge: lead-acid vs lithium

Depth of discharge is the share of a battery you use before recharging, and it is where battery chemistry changes the answer most. A flooded lead-acid or tubular battery — the standard IPS battery in Bangladesh — lasts longest when cycled to about 50% DoD; deep discharges every day can cut its life to a fraction of its rated cycles, which is why Trojan Battery and Battery University both treat 50% as the practical design limit (see Sources). Lithium (LiFePO4) banks tolerate 80% DoD routinely, so the same backup needs a much smaller nameplate bank: the 417 Ah lead-acid example becomes (500 × 4) ÷ (12 × 0.80 × 0.80) = about 260 Ah in lithium.

Smaller is not automatically cheaper or simpler. Lithium costs more upfront, needs a compatible charger profile and battery management, and not every IPS unit can charge it correctly. The calculator lets you switch battery type to compare the two sizes honestly — and lets you edit the DoD directly if your battery manufacturer specifies a different limit, since the manufacturer's figure always outranks a general rule.

Why real backup time is shorter than calculated

Plainly stated: these results are sizing estimates, not promises. Real backup time drops as batteries age — a two-year-old lead-acid bank may hold 70–80% of its original capacity — and it drops further in cold weather, when the true load is higher than the list you typed, and when a lead-acid battery is discharged quickly, because its effective capacity falls at high discharge rates (the Peukert effect). Self-discharge, cable losses and an inverter whose real efficiency is below its brochure figure each take a little more.

The defence is margin, applied in the right places: round battery counts up (this calculator always does), keep the 20% inverter headroom, and if the backup hours are critical — a home office, medical equipment, a shop that cannot close — size for about 25% more than the bare requirement and maintain the bank properly: correct charging, electrolyte checks on flooded batteries, and clean, tight terminals. A system sized exactly to the formula and then neglected will disappoint; a system sized with margin and maintained will usually beat its estimate when new and meet it years later.

Common IPS sizing mistakes

The classic error is sizing the battery in VA or watts instead of amp-hours: a "1,000 VA IPS with 200 Ah battery" tells you the inverter size and one battery — nothing about backup until voltage, efficiency and DoD are applied, which is the whole formula above. Second is forgetting depth of discharge and expecting a 200 Ah battery to deliver 200 Ah; at 50% DoD it delivers 100 usable Ah, and expecting double is the single most common cause of "my IPS backup is half what the shop said". Third is forgetting efficiency, which quietly removes another fifth.

Fourth, counting every appliance in the house instead of the outage load — heaters, kettles, irons and air conditioners belong on the mains-only circuit. Fifth, mixing old and new batteries in one bank; the old battery limits the new ones and fails early. Sixth, buying for today's load only: a bank is a five-to-ten-year purchase, so a modest allowance for one more fan or a bigger TV is cheaper now than a second bank later — as long as it is a deliberate allowance, not guesswork.

Wiring, installation and safety

An IPS bank stores enough energy to start a fire if it is shorted, and its AC output is mains voltage. Wiring and installation need a qualified electrician — this calculator sizes the system; it does not design your wiring. Battery cables must be thick enough for the DC current (which at 12 V is large: 500 W is over 40 amps before losses), fused close to the battery, and kept short. Flooded batteries release hydrogen while charging and need ventilation, no sparks or flames nearby, and care with electrolyte, which is sulphuric acid. Batteries are heavy, hold a charge after disconnection, and must be recycled at end of life, never dumped.

Changeover wiring deserves the same respect: the IPS output must never feed back into the mains grid, both for your household's safety and for the line workers repairing the outage. A properly installed system separates backup circuits from mains-only circuits at the distribution board. If any part of an installation quote seems to skip fusing, ventilation or changeover isolation to save money, treat that as a reason to change installer, not as a saving.

Limits: what this calculator cannot do

This calculator applies the standard sizing formulas with the values you enter. It does not measure your appliances, test your batteries, or know your inverter's true efficiency, surge rating or charger size. It assumes the load stays constant for the whole backup period — a fridge that cycles will stretch real backup beyond the estimate, while a load that grows will shrink it. It does not apply the Peukert correction for very high discharge rates, temperature corrections, or ageing allowances; the margin advice in this guide exists precisely because those effects are real.

It is not a substitute for the battery and IPS manufacturers' specifications, your local electrical rules, or a qualified electrician, who governs every real installation. Used inside those limits — planning a system, comparing lead-acid against lithium, checking a seller's quote against open arithmetic — it is exact: the same formula, the same worked example, reproducible by anyone with the numbers on this page.

Sources & References

The sizing formulas on this page are the standard inverter-battery sizing relations: Required Ah = (Load W × Backup hours) ÷ (Battery V × Efficiency × DoD) and VA = W ÷ power factor. The 50% lead-acid and 80% lithium depth-of-discharge defaults follow the battery-life guidance of the manufacturers and references above. Every figure in this guide was calculated with this page's own formulas — the 500 W, 4-hour worked example gives (500 × 4) ÷ (12 × 0.80 × 0.50) = 416.7 Ah — so you can reproduce each one exactly above.