What is voltage drop?
Voltage drop is the voltage lost as current flows through the resistance of the wire itself. Every conductor resists current a little, and that resistance, multiplied by the current, consumes voltage along the run — voltage the load at the far end never sees. A 120 volt supply at the panel can easily be 113 or 114 volts at the end of a long, thin, heavily loaded run, and the missing volts have not vanished: they were spent pushing current through the cable, warming it slightly on the way. This voltage drop calculator exists to put a number on that loss before the wire is bought and buried, using the standard voltage drop formula, a published wire size voltage drop table, and your choice of copper or aluminium, AWG or metric sizing.
The effect is invisible in short runs and decisive in long ones, because drop grows in direct proportion to distance and to current. Double the length and you double the drop; double the load and you double it again. That is why the same 12 AWG cable that serves a bedroom outlet perfectly can starve a workshop, a well pump, a detached garage or a long landscape-lighting run. It is also why low-voltage systems suffer most: a 6 volt loss is an annoyance on a 240 volt circuit, a problem on 120 volts, and half the entire supply on a 12 volt system. Anyone asking how to calculate voltage drop is really asking one question — will enough voltage be left at the load? — and this page answers it in volts, in percent, and against the guidelines designers actually use.
The voltage drop formula
The factor of 2 is the part people most often question, and it is pure geometry: current must travel out to the load on one conductor and back on another, so the circuit contains twice the one-way length of wire. You enter the one-way distance — panel to load — and the formula supplies the return trip. Three-phase is kinder: in a balanced three-phase system the conductors share the return duty, and the correct factor is the square root of 3, about 1.732, applied to the line-to-line voltage. This calculator switches the factor automatically when you change the phase selector, so the only way to get it wrong is to describe the circuit wrongly.
Underneath the table-based form sits the physicist's version, which the metric mode of this calculator uses directly: resistance equals resistivity times length divided by cross-sectional area, R = ρL ÷ A. Copper's resistivity is 1.724×10⁻⁸ Ω·m at 20°C and aluminium's is about 2.82×10⁻⁸ Ω·m, which is the entire reason aluminium conductors are larger for the same job. Both forms are Ohm's law — V = I × R — applied to the wire instead of the load, which is why pairing this page with the Ohm's Law Calculator in the related tools gives you the complete picture: one tool for the circuit, this one for the cable feeding it.
Worked example: 12 AWG vs 10 AWG at 100 feet
Take a 120 volt, 20 amp load, 100 feet one-way from the panel, on copper wire, single-phase. With 12 AWG, the table gives 1.588 Ω per 1,000 feet. The voltage drop formula gives Vdrop = 2 × 100 × 20 × 1.588 ÷ 1,000 = 6.35 volts. As a percentage, 6.35 ÷ 120 × 100 = 5.29%, and the load receives 120 − 6.35 = 113.65 volts. That fails the 3% branch-circuit guideline and even edges past the 5% total guideline — this run is too thin for its length and load, full stop. Every figure here is reproduced by the calculator above with its default values, so you can check the arithmetic yourself in seconds.
Now step up one size to 10 AWG, at 0.999 Ω per 1,000 feet: Vdrop = 2 × 100 × 20 × 0.999 ÷ 1,000 = 4.00 volts, which is 3.33%, leaving 116.00 volts at the load. Better — inside the 5% total guideline, though still a touch over the 3% branch-circuit target. One more step, to 8 AWG at 0.628 Ω per 1,000 feet, gives 2.51 volts or 2.09%, comfortably inside 3%. This little ladder is the everyday reality of wire size voltage drop decisions: each AWG step cuts resistance by roughly a fifth to a third, and on long runs those steps are the difference between equipment that works and equipment that merely almost works.
| Wire (copper) | Resistance Ω/1,000 ft | Voltage drop | Drop % | Voltage at load |
|---|---|---|---|---|
| 12 AWG | 1.588 | 6.35 V | 5.29% | 113.65 V |
| 10 AWG | 0.999 | 4.00 V | 3.33% | 116.00 V |
| 8 AWG | 0.628 | 2.51 V | 2.09% | 117.49 V |
AWG wire resistance table: copper and aluminium
The table below is the exact dataset this calculator uses in AWG mode — conductor DC resistance in ohms per 1,000 feet, following the widely published conductor resistance values used by US wire manufacturers and voltage-drop references (see Sources). Read it as the price of distance: every 1,000 feet of 12 AWG copper in the circuit costs 1.588 ohms, and your run uses a fraction of that — 100 feet out and 100 feet back is 200 conductor-feet, or a fifth of the table value, before the current is even applied. Aluminium's column runs about 1.65 times copper's at every size, the direct fingerprint of its higher resistivity.
| AWG | Copper Ω / 1,000 ft | Aluminium Ω / 1,000 ft |
|---|---|---|
| 14 | 2.525 | 4.164 |
| 12 | 1.588 | 2.620 |
| 10 | 0.999 | 1.650 |
| 8 | 0.628 | 1.038 |
| 6 | 0.395 | 0.654 |
| 4 | 0.248 | 0.411 |
| 3 | 0.197 | 0.326 |
| 2 | 0.156 | 0.258 |
| 1 | 0.124 | 0.205 |
| 1/0 | 0.0983 | 0.162 |
| 2/0 | 0.0779 | 0.129 |
| 3/0 | 0.0618 | 0.102 |
| 4/0 | 0.0490 | 0.0810 |
Two patterns in the table are worth internalising. First, the AWG scale is geometric: every three sizes, resistance roughly halves — 12 AWG at 1.588, 6 AWG at 0.395 is two such steps and almost exactly a quarter. Second, the gains flatten as wire gets huge: going from 3/0 to 4/0 saves only about 0.013 Ω per 1,000 feet, which is why very long, very heavy runs are solved with higher voltage or parallel conductors rather than ever-thicker single cables. Note also what the table is not: it is a resistance table for drop calculations, not an ampacity table. Whether a wire may legally and safely carry your current is a separate question answered by code ampacity tables, insulation ratings and breaker sizing — a wire can pass the drop test and fail the ampacity test, or the reverse, and both must pass.
Choosing a wire size for voltage drop
Start from the load, not the wire. Fix the supply voltage, the actual running current — not the breaker size, and not a nameplate maximum the equipment rarely reaches — and the true one-way distance, following the cable's real path with its bends and rises, not the straight-line distance on a plan. Enter those in the calculator with your preferred material and read the drop for the size you were hoping to use. If it lands inside your target — 3% for a branch circuit is the usual design aim — you are done. If not, step up one AWG size at a time and watch the percentage fall; the calculator's live update makes this a ten-second exercise rather than a page of arithmetic.
Then sanity-check the winner three ways. First, ampacity: confirm the chosen size is rated for the current in its installation conditions, because drop compliance never overrides heating limits. Second, the future: a run installed today for 12 amps may feed 20 amps in five years, and wire is cheap exactly once — while the trench or wall is open. Third, the alternatives: sometimes the right answer is not thicker wire but a shorter route, a relocated panel, a 240 volt circuit instead of 120 (the same drop in volts becomes half the percentage, and balanced loads often halve the current too), or splitting one long run into two shorter ones. Voltage drop problems are geometry problems, and geometry usually offers more than one fix.
The 3% and 5% guidelines — what they really are
The figures quoted everywhere — maximum 3% voltage drop on a branch circuit, maximum 5% total for the feeder and branch circuit combined — come from informational notes in the US National Electrical Code, attached to sections such as 210.19 for branch circuits and 215.2 for feeders. Informational notes are explanatory material: they state that conductors sized to these limits "provide reasonable efficiency of operation", but they are not enforceable code requirements, and this page labels them exactly that way. An installation at 5.29% — our 12 AWG worked example — is not automatically a code violation; it is a design that wastes energy, heats cable and short-changes the load, which is reason enough to fix it.
Why those numbers? At 3%, a 120 volt circuit still delivers 116.4 volts — inside the tolerance band most equipment is designed around — and the energy burned in the cable stays modest. At 10%, by contrast, a tenth of the power you paid for heats the walls instead of doing work, motors run hot and draw still more current, and lamps dim visibly. Treat 3% as the design target for the final branch circuit, 5% as the ceiling for the whole path from service to load, and be stricter where the load is sensitive: long motor runs, 12 volt systems, medical or audio equipment and EV charging all reward tighter limits. Your local code and a licensed electrician govern any real installation — the guideline check here is a planning compass, not a permit.
Single-phase, DC and three-phase drop
DC and single-phase AC share the same formula because their circuits are the same shape: one conductor out, one conductor back, the full load current in each. That is the factor of 2. Battery systems, solar DC runs, single-phase mains circuits and ordinary extension-cord maths all live here. If your supply is a battery, remember that its voltage also sags under load and falls as it discharges — the drop this calculator gives is the cable's share only, on top of whatever the source itself does.
Balanced three-phase replaces 2 with √3, about 1.732, and uses the line-to-line voltage. For identical wire, current and distance, a three-phase run drops less than a single-phase one — one of the quiet reasons industry standardised on it. The balance matters: a badly unbalanced three-phase load pushes current into the neutral and behaves worse than the formula suggests, and single-phase loads tapped from a three-phase supply should be calculated as single-phase for their own leg. When in doubt about which description fits your circuit, calculate both and design to the worse answer; the selector above makes that a two-click check.
Metric mode: mm² sizes and the resistivity formula
Outside North America, wire is sized by its actual cross-section in square millimetres — 1.5, 2.5, 4, 6, 10 mm² and upward — and drop is calculated from resistivity rather than a gauge table. Switch the size system to mm² and this calculator uses Vdrop = k × I × ρ × L ÷ A, with ρ = 1.724×10⁻⁸ Ω·m for copper or 2.82×10⁻⁸ Ω·m for aluminium at 20°C, L in metres and A converted from mm². As a rough bridge between the two worlds, 12 AWG is about 3.3 mm² and 10 AWG about 5.3 mm², so a 6 mm² metric conductor sits just above 10 AWG in performance — the calculator lets you verify that equivalence numerically instead of trusting conversion charts.
One honest asymmetry: the AWG table values are the published conductor resistances the US industry calculates with, while the metric mode computes from the 20°C resistivity constants. A conductor working hard at elevated temperature has higher resistance than either basis suggests — the next section covers that gap — so treat cross-mode agreement within a few percent as confirmation, and any large disagreement as a sign an input, not the physics, differs between the two runs.
Temperature: the moving part in every drop calculation
Resistance is not a constant of the metal; it climbs with temperature, for copper by roughly 0.39% per degree Celsius. A conductor loafing along at light load sits near ambient temperature, while the same conductor at full ampacity in a hot roof space can run at 60–75°C, carrying resistance a fifth or more above its cool value — and therefore dropping a fifth more voltage than a room-temperature calculation promises. This is the main reason real-world measurements on heavily loaded runs come in slightly worse than calculator estimates, and why designs that only just scrape inside 3% on paper deserve one more wire size in practice.
The calculator is transparent about its basis: AWG mode uses the standard published resistance table shown above, and metric mode uses the 20°C resistivity constants, both stated on the page. It does not apply a temperature correction, because the true conductor temperature depends on loading history, bundling, conduit and ambient conditions no web form can know. If your run will live hot and loaded — an attic feeder in a hot climate is the classic case — add margin: design to 2–2.5% by the calculator and let temperature spend the difference.
Common voltage drop mistakes
The classic error is doubling twice: entering the round-trip distance and letting the formula's factor of 2 count the return conductor again, which doubles the answer and buys wire two sizes too large. Enter one-way distance only. Second is calculating at breaker rating instead of load current: a 20 amp breaker feeding a 9 amp load drops at 9 amps, and sizing to the breaker wastes copper — though sizing to a realistic future load is wisdom, not waste, as long as it is a deliberate choice. Third is forgetting the percentage depends on voltage: the same 6.35 volt drop is 5.29% at 120 volts, 2.65% at 240 and a catastrophic 53% at 12.
Fourth, ignoring the feeder: the 5% total budget is spent by every segment in series — service drop, feeder and branch — and a branch circuit polished to 2% still fails the load if the feeder already spent 4%. Add the segments; this calculator handles one segment at a time, so run it per segment and sum the percentages. Fifth, trusting the shortest distance: cable follows walls, rises and detours, and a "60 foot" run is routinely 75 feet of wire. Measure the path, add a service loop allowance, and round up — distance errors flow straight through to the answer, undiluted.
Limits: what this calculator cannot do
Plainly stated: this calculator uses conductor resistance only. On long AC runs, inductive reactance adds to the effective impedance — increasingly so for large conductors in steel conduit — and load power factor changes how the drop divides between useful and wasted voltage. Neither is included, so for long feeders, large sizes or motor circuits, treat the result as a good first estimate and expect the full impedance-based calculation (the kind in NEC Chapter 9, Table 9) to differ somewhat. It also assumes balanced three-phase loads, steady current, and the stated resistance basis; it does not model battery sag, inverter behaviour, harmonic-rich loads or transient starting currents, which for motors can be five to seven times running current for the first moments.
It does not check ampacity, insulation temperature ratings, conduit fill, breaker sizing or any other code requirement, and it is not a substitute for the NEC, your local electrical code, or a licensed electrician, who govern every real installation. Used inside those limits — planning runs, comparing wire sizes, checking a design before it is built, learning how the formula behaves — it is exact: the same published resistance data and the same formula, applied instantly, with its worked example open for anyone to verify by hand.
Sources & References
- Copper Development Association — Electrical applications of copper (conductor properties and uses)
- NFPA — NFPA 70, National Electrical Code (the 3% / 5% informational-note guidance)
- Southwire — Wire and cable products and voltage drop resources (AWG resistance table basis)
- Cerro Wire — Resources (conductor data and voltage drop guidance)
- Mike Holt Enterprises — NEC training and voltage drop articles
- Wikipedia — American wire gauge (AWG sizes and conductor data)
- Wikipedia — Voltage drop (definitions, formulas and allowable-drop practice)
The AWG resistance table on this page follows the widely published conductor resistance values used by US wire manufacturers and voltage-drop references, including Southwire's published data: 12 AWG copper 1.588 Ω per 1,000 ft and 10 AWG copper 0.999 Ω per 1,000 ft. Every figure in this guide was calculated with this page's own formula — Vdrop = k × L × I × R — so you can reproduce each one exactly above.