What is inverter battery backup?
Inverter battery backup is the runtime you get from a battery bank through an inverter or UPS when the mains power fails: the usable energy stored in the bank, in watt-hours, divided by the load you are running, in watts. A home inverter, an IPS (Instant Power Supply) and a UPS all do the same basic job. While mains power is present they pass it through and charge their batteries. When power cuts, the inverter converts battery DC into household AC and your fans, lights, router, TV or computer keep running. The only question that matters at buying time is how long that lasts — and that is exactly what this inverter battery backup calculator answers, in both directions.
People search for this calculation as a ups backup time calculator, battery backup calculator, inverter battery calculator or battery ah calculator for inverter — all the same arithmetic, covered here with one engine, two modes and the formulas shown openly, so you can check a seller’s promise or your own existing system by hand. It is built first for India, where inverter backup is a daily household decision, but the physics is identical everywhere.
The two modes: backup time and required battery
Backup Time mode starts from a system you own or are about to buy. You build the total load from a preset appliance list — ceiling fan, LED light, LED TV, fridge, laptop, Wi-Fi router and a custom row — or you type the total watts directly. You then enter the battery bank voltage (12, 24 or 48 V), the amp-hour rating of one battery, how many batteries you have, the battery type and the inverter efficiency. The calculator combines the batteries into a bank, applies depth of discharge and efficiency, and returns the backup in decimal hours and in hours and minutes, together with the usable watt-hours and the minimum inverter VA for that load.
Switching modes is the normal way to shop: size the bank in Required mode, then drop the real batteries you can buy into Backup mode and see the runtime they truly deliver.
The backup formula, term by term
A battery rated 12 volts and 150 amp-hours stores, on paper, 12 × 150 = 1,800 watt-hours. Almost none of that headline figure is honestly available. The first reduction is depth of discharge (DoD) — the share you may use without wrecking battery life: 50% for flooded lead-acid and tubular, 80% for lithium and LiFePO4. The second is inverter efficiency: converting DC to AC wastes energy as heat, typically 10–20%, so this calculator defaults to 85% and lets you change it.
Usable watt-hours are therefore V × Ah × DoD × efficiency, and backup hours are usable watt-hours divided by load in watts. Every term is visible and editable here because every term is where a careless estimate inflates the answer: ignore DoD and you double a lead-acid system’s promised backup; ignore efficiency and you add another optimistic fifth.
Worked example: how long does a 150 Ah battery last at 500 W?
Take the most common Indian home setup asked about: a 500 W load, a 12 V system, one 150 Ah lead-acid battery, 50% depth of discharge and 80% inverter efficiency. Usable energy = 12 × 150 × 0.50 × 0.80 = 720 watt-hours. Backup = 720 ÷ 500 = 1.44 hours, shown as 1 hour 26 minutes. You can reproduce this exactly above: in Backup Time mode enter a 500 W load, 12 V, 150 Ah, 1 battery, lead-acid and 80% efficiency.
Under kinder assumptions the same battery seems to grow. At this page’s default 85% efficiency it gives 765 Wh and about 1.53 hours. As lithium at 80% DoD and 85% efficiency it gives 1,224 Wh, about 2.45 hours. And a promise of the full nameplate 1,800 Wh — 3.6 hours — has skipped both DoD and efficiency entirely. The battery never changed; only the honesty of the arithmetic did.
Worked example: battery for 800 W for 3 hours
Now run the problem backwards, the way you should before buying. The job is 800 W for 3 hours on a 24 V system, with lead-acid depth of discharge of 50% and inverter efficiency of 85%. Required Ah = (800 × 3) ÷ (24 × 0.85 × 0.50) = 2,400 ÷ 10.2 = 235.3 Ah at 24 V. That is the minimum bank; real batteries come in standard sizes, so the practical answer is two parallel strings of 150 Ah batteries — each string being two 12 V batteries in series for 24 V — which is 4 batteries in total and 300 Ah of nameplate capacity, with sensible margin above the 235.3 Ah minimum.
The inverter half of the same job is just as important. VA = load W ÷ power factor = 800 ÷ 0.8 = 1,000 VA minimum. A 1,000 VA inverter is the floor, not the target: anything with a motor in that 800 W load will surge on starting, and a unit run continuously at its limit runs hot. Most buyers in this position choose the next standard size up. This calculator shows the 1,000 VA minimum guidance on every result, in both modes, so the inverter is never forgotten while attention is on the batteries.
Building your load: typical appliance wattages
Every backup calculation stands or falls on the load figure, so build it carefully. Size for the load that will genuinely run together at the worst moment — a hot evening outage with every fan on — not for a hopeful average. Read rating plates where you can: the watts printed on the appliance, or amps multiplied by volts, always beat a generic table. The table below gives typical running wattages for common appliances; they are typical values for planning, clearly labelled as such, and they are the same figures used by the preset list in the calculator. Your own model may differ, sometimes by a lot, especially for older fans, large televisions and anything with a heating element.
| Appliance | Typical running watts | Note |
|---|---|---|
| LED bulb or tube light | 9–12 W | Per light; the preset uses 12 W |
| Ceiling fan | 75 W | Older fans 90–100 W; BLDC fans about 28–35 W |
| LED TV | 80–100 W | Mid-size set; the preset uses 100 W; larger sets draw more |
| Wi-Fi router and ONT | 10–15 W | The preset uses 10 W for the router |
| Laptop | 45–65 W | While charging and in use |
| Desktop computer with monitor | 150–250 W | Gaming systems can draw far more |
| Fridge | 100–200 W | Running watts; the preset uses 150 W; the compressor cycles and surges on start |
| Washing machine | 300–500 W | Motor load; heater models draw much more on hot cycles |
| Microwave oven | 800–1,200 W | Usually kept off the backup circuit |
| Room air conditioner (1.5 ton) | 1,100–1,700 W | Plus a large starting surge; only on suitably sized systems |
Two patterns matter. The comfort backbone — fans, LED lights and the router — is light: three fans, six lights and a router draw about 307 W. Heating and large motor appliances dominate everything else, so keep kettles, irons and heaters on mains-only circuits and spend the battery budget on loads that make an outage bearable.
Battery types and depth of discharge
Flooded lead-acid and tubular batteries are the standard inverter batteries across India: affordable, widely available, tolerant of rough handling and easy to recycle. Their weakness is depth of discharge. Cycle one to 50% DoD and it can deliver its rated service life; drain it to 80 or 90% daily and its life collapses. That is why this calculator plans lead-acid and tubular banks at 50% DoD — not because the battery cannot physically give more on one occasion, but because a sizing plan that spends the battery’s life is not a plan. Choose the tubular option and the calculator applies the same 50% figure, since tubular plates improve cycle life at a given DoD rather than licensing a much deeper one.
Lithium and LiFePO4 batteries invert the trade-off: more expensive per amp-hour, but about 80% of capacity is honestly usable, voltage holds better under load, the Peukert effect is minimal and recharging is faster. The 235.3 Ah lead-acid requirement above becomes (800 × 3) ÷ (24 × 0.85 × 0.80) = about 147 Ah in lithium. The cautions are upfront cost and compatibility — the inverter needs a suitable lithium charging profile and the battery its own management system. If your maker specifies a different DoD, use Custom DoD and enter it: the manufacturer’s figure outranks any general rule.
Bank voltage, series and parallel — kept simple
Home batteries are almost always 12 V units, whatever the system voltage. Wire two in series and voltages add while amp-hours stay the same: a 24 V, 150 Ah string. Wire strings in parallel and amp-hours add while voltage stays the same. Higher system voltages exist mainly to cut current: 800 W drawn from a 12 V bank means roughly 78 amps from the batteries after efficiency losses, while the same load at 24 V needs about half that, and at 48 V about a quarter — thinner cables, less heat and smaller voltage losses. That is why larger Indian home systems are usually 24 V and why commercial UPS banks run higher still.
To keep this calculator simple, it works from total bank voltage and total amp-hours: series count is bank V ÷ 12, and bank Ah is one battery’s Ah multiplied by the parallel strings (battery count ÷ series count). Keep the count a multiple of the series count — 2 or 4 batteries on 24 V, 4 or 8 on 48 V — and keep every battery the same model, age and capacity, wired with equal-length cables, or the weakest battery drags the rest down. Victron’s Wiring Unlimited guide in the sources covers bank wiring in depth.
Inverter VA, power factor and surge
Inverters and UPS units are rated in VA (volt-amps); your appliances are labelled in watts. The bridge between them is the power factor: watts = VA × power factor, and 0.8 is the standard planning figure for home systems. So the minimum inverter size is VA = W ÷ 0.8 — 500 W needs at least 625 VA, and the 800 W worked example needs at least 1,000 VA. This calculator displays that minimum on every result rather than hiding it, because an undersized inverter fails immediately and completely, while an undersized battery merely fails early.
The minimum is a floor for three reasons: motor starting surges, future load growth, and cooler, longer-lived operation with headroom. Check also for pure sine wave output (preferred for motors and sensitive electronics) and the built-in charger size in amps, which decides how fast a drained bank refills before the next outage — a mismatch no battery calculation can fix afterwards.
Why real backup is shorter: ageing and the Peukert effect
Plainly stated: every figure on this page is an estimate for planning, not a guarantee. Real backup falls as batteries age — a lead-acid bank a few years old may hold only 70–80% of its original capacity, less if it has been poorly charged or left discharged. It falls in cold weather, when chemical reactions slow. It falls when the true load is higher than the list you typed, which is common when a fridge, a set-top box or a charger was forgotten. And for lead-acid batteries it falls at high discharge rates because of the Peukert effect: capacity ratings are measured at a gentle 20-hour discharge, and drawing the same battery down in one or two hours yields noticeably fewer amp-hours than the label promises. Lithium batteries suffer far less from this effect, one of their genuine advantages for short, heavy backups.
The defence is margin: round battery counts up, as Required mode does when it turns 235.3 Ah into a 300 Ah practical bank, keep inverter headroom, and maintain the bank — correct charging, distilled-water top-ups on flooded batteries, clean tight terminals. If the backup protects something critical, size about 25% above the bare calculation and test the real runtime once, with a clock, before depending on it.
Common backup sizing mistakes
The classic error is quoting the nameplate as the backup: “150 Ah battery” turned directly into hours by dividing 1,800 Wh by the load, skipping both DoD and efficiency, overstates a lead-acid system’s runtime by more than double. Second is confusing VA with watts and buying a 1,000 VA inverter for a 1,000 W load, when the power factor alone demands 1,250 VA before any headroom. Third is counting nameplate amp-hours at the wrong voltage — comparing a 24 V bank’s amp-hours directly with a 12 V bank’s, when the 24 V figure represents twice the energy per amp-hour.
Fourth, forgetting the surge: a system that runs a fridge happily may still fail to start it. Fifth, mixing old and new batteries, so the old battery limits the new ones. Sixth, ignoring recharge time: where gaps between outages are short, the limit is often how much charge the charger can replace, not bank size. Each mistake is visible in advance with the arithmetic on this page.
Wiring, installation and safety
A battery bank stores enough energy to start a fire if it is shorted, and an inverter’s output is mains voltage. Wiring and installation need a qualified electrician. This calculator sizes a system; it does not design your wiring. DC cables at 12 V carry very large currents and must be thick, short and fused close to the battery. Flooded batteries release hydrogen while charging and need ventilation and freedom from sparks and flames, and their electrolyte is sulphuric acid. Changeover wiring must never allow the inverter output to feed back into the mains grid — for your household’s safety and for the line workers repairing the outage. Batteries are heavy, remain live after disconnection, and must be recycled at the end of their life, never dumped. If an installation quote saves money by skipping fusing, ventilation or changeover isolation, change the installer, not the safety items.
Limits: what this calculator cannot do
This calculator applies the standard backup formulas to the values you enter. It does not measure your appliances, test your batteries, or know your inverter’s true efficiency curve, surge rating or charger size. It assumes a constant load for the whole backup period: a cycling fridge will stretch real runtime beyond the estimate, while a growing load will shrink it. It does not apply a Peukert correction, temperature corrections or an ageing allowance — the margin advice in this guide exists precisely because those effects are real. It is not a substitute for the battery and inverter manufacturers’ specifications, your local electrical rules, or a qualified electrician. Used inside those limits — planning a system, comparing lead-acid against lithium, checking a seller’s runtime promise against open arithmetic — it is exact, and every worked example on this page can be reproduced in the calculator above.
Related calculators: sizing a complete home system from scratch? The IPS Calculator sizes battery and inverter together from an appliance list. Checking cable losses on a long battery or solar run? Use the Voltage Drop Calculator.
Sources & References
- Victron Energy — Wiring Unlimited (battery bank wiring, series and parallel connections, system design)
- Victron Energy — Inverters and inverter/chargers (inverter sizing, efficiency and surge ratings)
- Battery University — Charging lead-acid batteries (BU-403)
- Battery University — How to prolong lithium-based batteries (BU-808, depth of discharge and cycle life)
- Trojan Battery — Battery maintenance (watering, charging and care for flooded lead-acid batteries)
- Exide Industries — Inverter batteries (tubular battery ranges for home inverter use in India)
- Luminous Power Technologies — Inverters and batteries (Indian home inverter and battery ranges and guidance)
Sources note: all seven sources above were checked directly and returned HTTP 200 at the time of writing; no substitutions were needed. The Luminous link points to the manufacturer’s official home page because its deeper product paths move frequently; the guidance relied on here is its published inverter and battery range information. The formulas on this page are the standard relations stated in the guide: usable Wh = V x Ah x DoD x efficiency, backup hours = usable Wh / load W, required Ah = (load W x hours) / (V x efficiency x DoD), and VA = W / 0.8. The 50 percent lead-acid and tubular and 80 percent lithium depth-of-discharge defaults follow the battery-life guidance of the manufacturers and references above. Appliance wattages in the guide table and preset list are labelled typical running figures for planning, not measurements. Every worked figure was calculated with this page’s own formulas — 12 x 150 x 0.50 x 0.80 = 720 Wh and 720 / 500 = 1.44 hours; (800 x 3) / (24 x 0.85 x 0.50) = 235.3 Ah; 800 / 0.8 = 1,000 VA — so you can reproduce each one exactly above.